BQ226

Modbus Temperature and Humidity Sensor

BQ226 Modbus Temperature and Humidity Sensor

Reports temperature and relative humidity over RS485 Modbus RTU. Connect a 10 kΩ NTC probe for a second temperature reading.

The enclosure is sealed and the sensor uses a removable filter. Set the Modbus address and baud rate with the BQTEK configuration utility. A cable can keep the device outside the measurement area, for example in a cold store. Avoid prolonged condensation and corrosive environments.

Visit the BQTEK product page for more information, images and documentation.

Product Page(opens in a new tab)

Technical Specifications

Power supply
12-24V DC 20mA
Resolution
14-bit
Temperature range (built-in probe)
-20 °C to +55 °C
Temperature range (cabled probe)
-30 °C to +80 °C
Temperature range (10 kΩ NTC)
-50 °C to +140 °C
Temperature accuracy (digital sensor)
±0.2 °C
Temperature accuracy (10 kΩ NTC)
±1 °C
Humidity range
0% to 99% RH
Humidity accuracy
±2.0 %RH
Serial port
RS485
Protocol
Modbus RTU
Operating temperature
-20 °C to +50 °C
Terminal block type
Plug-in terminal block (5.08mm)
Enclosure type
Sealed plastic enclosure
Dimensions (BQ226-A-00)
100 x 174 x 39 mm